Acme Engineering Products CEJW Series High Voltage Immersed Electrode Hot Water Boiler – Electric Boiler

Acme Engineering Products offers hot water boilers based on a proven design for building complexes, commercial structures, and light industry. Their boilers can be connected directly to the high voltage power distribution network.

Any voltage up to 20 KV, 3 phases, 3 wires, and centerline grounded line.

  • Capacity range: 2500 to 68,000 KW
  • Electric Power Supply Voltage: 4160 to 25000 V
  • Maximum Operating Temperature for Standard Models: 180 °C (360 ° F)
  • Operating pressure: 3 to 14.5 bar (50 to 200 psi)
  • Power Feeds (Current Passage) assembled and certified for 42000 V and 16 bar (230 psi) for any operating voltage
  • Fast Response: 0 to 100 % capacity in:
    • Hot State: 1 minute
    • Cold to Hot state: 15 to 25 minutes (depends on the size)
  • Economical even for capacities between 2 to 6 MW
  • Simple controls
  • Can be added to existing systems and is suitable for optional water storage facilities
  • Ability to take advantage of low off-peak electricity rates and demand swings

Hot Water Electric Boilers

Acme Engineering Products offers hot water boilers based on a proven design for building complexes, commercial structures, and light industry. Their boilers can be connected directly to the high voltage power distribution network.

Any voltage up to 20 KV, 3 phases, 3 wires, and centerline grounded line.

  • Capacity range: 2500 to 68,000 KW
  • Electric Power Supply Voltage: 4160 to 25000 V
  • Maximum Operating Temperature for Standard Models: 180 °C (360 ° F)
  • Operating pressure: 3 to 14.5 bar (50 to 200 psi)
  • Power Feeds (Current Passage) assembled and certified for 42000 V and 16 bar (230 psi) for any operating voltage
  • Fast Response: 0 to 100 % capacity in:
    • Hot State: 1 minute
    • Cold to Hot state: 15 to 25 minutes (depends on the size)
  • Economical even for capacities between 2 to 6 MW
  • Simple controls
  • Can be added to existing systems and is suitable for optional water storage facilities
  • Ability to take advantage of low off-peak electricity rates and demand swings

These Electrode Boilers have unlimited application possibilities wherever a need for process or space heating exists. A partial list of possible uses includes:

  • Office and apartment buildings
  • Hospitals, schools, hotels
  • Food processing plants
  • Clothing and textiles plants
  • Industrial plants
  • Plastic and chemical plants
  • Mining operations
  • Power plants for District Heating
  • Car Manufacturing

The CEJW boilers convert virtually 100% of the electrical energy into heat. Automatic load and temperature controls provide step-less control over an output range from 10 to 100%.

  • Economical installation
  • Lower operating costs
  • Safer operation
  • Minimal maintenance
  • Environmentally friendly
  • Pressure vessel, ASME (Section I or IV) design, CRN/U stamp pressure vessel registration certificate or CE/PED required
  • Complete assembled Power feeds tested and certified for 16 bar (230 psi) and 42 KV
  • Boiler actuator and capacity control system
  • Large DN 500 (20”) Manhole
  • Sheet metal jacket and 100 mm (4”) ceramic fiber thermal insulation
  • Safety cage surrounding high voltage connections
  • Safety valve(s)
  • Manual drain (initial fill-up) valve
  • Automatic air vent

All of their Immersed Electrode Boilers are guaranteed for one year in operation or 18 months after shipment against defective workmanship and material. The guarantee is limited to the replacement of defective parts only when returned, prepaid, to the factory. A copy of the guarantee is available on request.

Acme Engineering Products, electric boiler, CEJWS-6 Electrode Boiler

Standard Equipment for Model CEJW

Mechanical (Base):

  • Pressure vessel, A.S.M.E design, CRN – pressure vessel registration certificate
  • Complete assembled Power feeds and Internal parts
  • Boiler actuator and capacity control system
  • Manhole 14 x 18 inches
  • Sheet metal jacket and thermal insulation
  • Cage surrounding high voltage connections

Mechanical (Heating loop design):

  • Vertical Inline Centrifugal pump(s)
  • Heat-exchanger, water to water
  • Expansion tank

Plumbing (Base):

  • Safety valve(s)
  • Manual blowdown and drain valve
  • Automatic air vent

Plumbing (Heating loop design):

  • Butterfly isolating valves, for boiler, heat-exchanger, and centrifugal pump
  • Piping for the loop
  • Y strainer, located on the pump suction pipe
  • Make up water system, connected to the Expansion tank-includes pump, y strainer, check valve, and two isolating gate valves
  • Chemical feed fitting, located on the pump suction pipe equipped with an isolating gate valve

Electrical:

  • Neutral terminal
  • Electrode terminal enclosures
  • Electrodes
  • Circulation pump motor and motor starter

Control:

  • Free-standing control panel
  • Pre-programmed electronic processor
  • Shield position indicator
  • Boiler pressure gauge
  • Boiler temperature gauge
  • Operating temperature control
  • High-temperature limit
  • High conductivity detection
  • Temperature transmitter
  • Water flow switch
  • Low water level detection

Optional items:

  • Supply circuit protective relays
  • Supply circuit switchgear
  • Special valves
  • Special instrumentation
  • Chemical feed systems
  • Water treatment equipment

All specifications are subject to change without notice. Installation, maintenance, operating, and any other instructions furnished with the equipment must be carefully followed by installers, owners, and users.

Shipping Models CEJW series: The unit must be laid down for shipment requiring some disassembly. Valves, trim, water level controller, electrodes, and actuator will be removed for shipping and require field installation. The unit may then be field-connected to feedwater, electric power, and the control panel.

Water Treatment: All boilers require adequate water quality as determined by conductivity, pH, softness, and chemical content. The type and degree of water treatment will be determined by local water quality, type of boiler, nature of operation, and quantity of raw makeup water required. It should be noted that the conductivity of the boiler water, alkalinity, pH, and chemical content increases as steam is generated. Most water supply systems are suitable for use with ACME Electrode Boilers when supplied with proper water treatment. A complete water analysis must be furnished to ACME for review to ensure proper water quality.

ACME Immersed Electrode Boilers for every application

These Immersed Electrode Boilers have unlimited application possibilities wherever a need for process or space heating exists. A partial list of possible uses includes:

  • Office and apartment buildings
  • Hospitals, schools, hotels
  • Food processing
  • Clothing and textiles plants
  • Industrial plants
  • Mining operations
  • Power plants

Electrical requirements: The CEJW boiler can be connected directly to the high voltage power distribution network. Any voltage up to 13.5 KV, 3 phases, 3 wires, and centerline grounded line. The boiler shell and cage must be grounded to the building steel and ground mat.